Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a036 Power
phase
loss
Critic
al
Any of
three
phase AC
voltages is
50 V or
less when
the alarm
detection
delay
expires.
1. The power grid is
unstable.
2. The surge
protection board is
faulty if
configured.
3. The main power
supply or the comp
driver supply is
connected
improperly.
1. Check the
power grid.
2. Maintain or
replace the
surge
protection
board.
3. Check the
main power
supply or
cables to the
comp driver.
a037 Power
phase
reverse
Critic
al
The surge
protection
and
filtering
board
detects an
incorrect
angle
among
three
phases
when the
alarm
detection
delay
expires.
1. The power grid is
unstable.
2. The surge
protection board is
faulty.
1. Check the
power grid.
2. Maintain or
replace the
surge
protection
board.
a042 Remot
e
shutdo
wn
Critic
al
The
remote
power-off
switch
polarity is
different
from the
preset
polarity.
1. The remote
shutdown dry
contact is
triggered.
2. The cables to the
remote shutdown
dry contact is
faulty.
1. Check the
status of the
remote
shutdown dry
contact.
2. Check the
cables to the
remote
shutdown dry
contact.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
173