Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a033 Power
phase
C
underv
olt
Major The AC
voltage of
phase C is
greater
than 50 V
and less
than the
low
voltage
alarm
threshold
when the
alarm
detection
delay
expires.
1. The power supply
voltage is lower
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
a034 Power
overfre
q
Major The AC
frequency
is greater
than the
high
frequency
alarm
threshold
when the
alarm
detection
delay
expires.
1. The power grid is
unstable.
2. The surge
protection and
filtering board is
faulty.
1. Check the
power grid.
2. Replace the
surge
protection
and filtering
board.
a035 Power
underf
req
Major The AC
frequency
is less
than the
low
frequency
alarm
threshold
when the
alarm
detection
delay
expires.
1. The power grid is
unstable.
2. The surge
protection and
filtering board is
faulty.
1. Check the
power grid.
2. Replace the
surge
protection
and filtering
board.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.