Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a028 Power
phase
A
overvo
lt
Major The AC
voltage of
phase A is
greater
than the
alarm
threshold,
and the
alarm
detection
delay
expires.
1. The power supply
voltage is higher
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
a029 Power
phase
B
overvo
lt
Major The AC
voltage of
phase B is
greater
than the
alarm
threshold,
and the
alarm
detection
delay
expires.
1. The power supply
voltage is higher
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
a030 Power
phase
C
overvo
lt
Major The AC
voltage of
phase C is
greater
than the
alarm
threshold,
and the
alarm
detection
delay
expires.
1. The power supply
voltage is higher
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
170