Parameter
Setting Method
Gateway
Set according to the actual plan.
----End
5.4.5 Setting Communications Parameters (Modbus Settings)
Context
●
To set communications parameters, log in as the admin user.
●
If Link mode is Server, a smart cooling product can be accessed by a
maximum of two element management system (EMS) clients at the same
time. If Link mode is Client, a smart cooling product can be connected only
to the EMS with the corresponding IP address. If Link mode is Server and
client, a smart cooling product can be accessed by a maximum of two EMS
clients and connect to the EMS with the corresponding IP address at the same
time.
shows the screen for setting the Modbus communications parameters.
Figure 5-8 Setting Modbus
Setting Parameters for Modbus RTU
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
is displayed.
Step 2 Set parameters for Modbus RTU.
Table 5-4 Modbus RTU parameter settings
Parameter Setting
Setting Method
Baud rate
9600, 19200
Set the baud rate as required. The value should be
consistent with that set on the EMS.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
99