Paramete
r
Description
Configuration
Principle
Default Value
Total
number
of units
Number of the
smart cooling
products in this
group (1 to 32 can
be set).
Total number of the
smart cooling
products in this
group.
3
Number
of
running
units
Number of running
units in a group. The
value ranges from 1
to Total number of
units.
The master unit
assigns the devices
to be active units by
the device number,
beginning with the
address 1 until to
Number of running
units. The rest will
become the standby
ones.
2
Rotation
Disable or enable
the active and
standby smart
cooling products to
change identity after
a certain time,
maximizing their
service life.
This function is
recommended when
the heat is even.
Disable
Rotation
period
Rotation days (1–
30).
7 by default.
7 day(s)
Rotation
time
24 hours in a day
(0–23).
0 by default.
0
Forced
rotation
Forced rotation
specifies whether to
enable a forcible
rotation on the
group before the
specified rotation
time. After a forced
rotation, the
accumulated time is
recalculated.
This item is set to
No by default. If
forced rotation is
required, the
function is set to
Yes.
No
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
108