Parameter Setting
Setting Method
Communic
ation
address
1–255
Set the communication address of the smart
cooling product as planned. The EMS
communicates with the smart cooling product
through this address, and the communication
addresses of two smart cooling products
connecting to the same EMS must be unique.
----End
Setting Parameters for Modbus TCP
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
is displayed.
Step 2 Set parameters for Modbus TCP.
Table 5-5 Modbus TCP parameter settings
Parameter Setting
Setting Method
Link mode
Server,
Client,
Server and
client
● If you set Link mode to Server, the smart
cooling product, as a server, supports two client
connection and establishes communication.
● If you set Link mode to Client, the smart
cooling product, as a client, can connect to a
remote server and establish communication.
● If you set Link mode to Server and client, the
smart cooling product, as a server, supports two
client connection and establishes
communication. In addition, the smart cooling
product, as a client, can connect to a remote
server and establish communication.
Client
encryption
Enable,
Disable
This parameter is configurable when Link mode is
set to Client.
Server
encryption
Enable,
Disable
This parameter is configurable when Link mode is
set to Server.
NMS IP
address
N/A
Enter the actual IP address of the EMS. IP addresses
of the display panel, EMS client, and EMS server
must be unique. This parameter is configurable
when Link mode is set to Client.
NMS port
number
N/A
It is recommended that you retain the default
value. If you need to change the value, enter a
value as required. This parameter is configurable
when Link mode is set to Client.
----End
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
100