Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a021 Humid
ifier
locked
Critic
al
The
infrared
humidifier
water pan
has
generated
three dry
heating
alarms
within
one hour.
The a020 humidifier
pan no water alarm is
generated frequently.
Reference to the
solutions for the
a020 humidifier
pan no water
alarm.
a022 Humid
ifier
exceed
runtim
e
Warni
ng
The
cumulativ
e running
period of
the
infrared
humidifier
is greater
than or
equal to
the alarm
threshold.
The accumulated
runtime of the
humidifier exceeds the
alarm threshold.
Maintain or
replace the
humidifier and
clear the
accumulated
runtime.
a023 Elec
heater
HT
Major The
electric
heater
overtemp
erature
switch is
triggered,
and the
airflow
loss
differentia
l pressure
switch is
closed
and does
not
recover
for N s.
1. Temperature
switch probes are
located
inappropriately.
2. The cables to the
temp switch of the
electric reheat are
loose or damaged.
3. The temperature
switch is faulty.
4. The manual reset
temperature switch
is not reset.
5. The indoor fans are
faulty.
1. Adjust the
positions of
the
temperature
switch probes.
2. Check the
cables to the
temp switch
of the electric
reheat.
3. Maintain or
replace the
temperature
switch.
4. Reset the
manual reset
temperature
switch.
5. Maintain or
replace the
indoor fans.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
167