4.2.3 Procedure to Partially Charging in Refrigerant
Prerequisites
●
Before charging in refrigerant, ensure that the air is exhausted from the hose
connecting to the refrigerant cylinder.
●
Charge in refrigerant (R410A) after checking that the cooling system does not
leak and the vacuum meets the requirements.
●
Partially charge in refrigerant from the high pressure needle valve.
Context
This section describes how to partially charge refrigerant, using the NetCol8000-
A050 as an example.
Procedure
Step 1 Charge in refrigerant from the high pressure needle valve. To prevent the liquid
refrigerant charge directly to the compressor, you can perform the following
operations.
Step 2 If no low-temperature component is installed on the outdoor side, close the high
pressure valve and low pressure valve shown in
. If low-temperature
component is installed on the outdoor side, close the high pressure needle valve,
low pressure needle valve, and liquid pipe needle valve shown in
.
Step 3 Disconnect the vacuum pump, connect the refrigerant steel vessel.
NO TICE
Never move the pipe or steel vessel when charging in refrigerant. Otherwise, the
value on the electronic balance is influenced.
If the R410A refrigerant is provided by Huawei, put the refrigerant steel vessel
upside down when charging in the refrigerant. If the refrigerant is not provided by
Huawei, check with the refrigerant provider whether the steel vessel has a siphon.
If the vessel has a siphon, put it upside up when charging in refrigerant. If the
vessel has no siphon, put it upside down when charging in refrigerant. These
measures ensure that the refrigerant is charged in the liquid form.
NO TE
The refrigerant cylinder can be raised to accelerate the refrigerant charging.
1. Check whether the low-temperature component is installed on the outdoor
side.
–
If no low-temperature component is installed on the outdoor side,
charging refrigerant into the system from the high pressure needle valve
and low pressure needle valve at the same time.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual