The fault diagnosis system automatically displays the information of the
current fault, which facilitates the maintenance.
●
The NetCol8000-A provides abundant external ports such as RS485 ports, fast
Ethernet (FE) ports, and USB ports that are protected by a security
mechanism.
●
The smart cooling product supports a maximum number of 500 alarms.
2.2.3 Monitoring System
The monitoring system provides logic control, data collection, control delivering,
alarm reporting, data storage, user right management, and teamwork. It can
connect to your monitoring system over a northbound port (RS485) for remote
management.
The NetCol8000-A series products can be networked over a controller area
network (CAN) bus to perform the teamwork, which efficiently save energy and
prolongs the service life.
shows the networking diagram for the monitoring system.
Figure 2-7 Network diagram for the monitoring system
2.2.4 Ports
The following table lists NetCol8000-A series product ports.
Table 2-3 Ports of the NetCol8000-A series product
Ports name
Specifications
Liquid pipe of refrigerant
Inside diameter 5/8 in. (15.9 mm)
Discharge pipe of refrigerant
Inside diameter 7/8 in. (22.3 mm)
Condensate drainpipe
BSPP 3/4 in.
Water pipe inlet of the humidifier
BSPP 3/4 in.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
2 Product Description
Issue 12 (2020-10-28)