background image

1

Installation Instructions

ECD-SRT12TA-D2, ECD-SRT34TA-D2, ECD-SRT05TA-D2 Series

Read these instructions completely before attempting to install the Vertical 

Accessory Ultra Low Leak Economizer.

CONTENTS

Safety Consideration . . . . . . . . . . . . . . . . . . . . .1

General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Economizer Sensor Usage. . . . . . . . . . . . . . . . . . . . .2

Accessories List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8 

W7220 Menu Structure. . . . . . . . . . . . . . . . . . . . .9-12 

Controller  Setup  and  Configuration.  .  .  .  .  .  .  .13-15 

Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . .17

Barometric Relief and Return Pressure

Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

*Jade W7220 Controller Addendum

*Certificate of Acceptance

Use QR Code Above to Access

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be 

hazardous dur to system pressure and electrical components. Only 

trained  and  qualified  service  personnel  should  install,  repair,  or 

service air-conditioning equipment.
Untrained personnel can perform the basic maintenance funtions. 

All other operations should be performed by trained service 

personnel. When working on air-conditioning equipment, observe 

precautions in the literature, tags, and labels attached to the unit, 

and other safety precautions that may apply.
Follow allsafety codes. Wear safety glasses and work gloves. Use 

quenching cloth for unbrazing operations.
It is important to recognize safety information.  This is the safety-

alert symbol      .  When you see this symbol on the unit and in 

instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, 

and NOTE.  These words are used with the safety-alert symbol.

DANGER  identifies  the  most  serious  hazards  which 

will

 result 

in severe personal injury or death.  WARNING signifies hazards 

which 

could

 result in personal injury or death.  CAUTION is used 

to identify unsafe practices, which 

may

 result in minor  personal 

injury or product and property damage.  NOTE is used to highlight 

suggestions which 

will

 result in enhanced installation, reliability, or 

operation.

Small Rooftop Products

 

Select 3 to 12 ½ Tons

Accessory Ultra Low Leak Vertical Economizer

!

MicroMetl

California

& ASHRAE

Code

Compliant

WARNING

Electrical Shock Hazard

Can cause severe injury, death or property damage. Disconnect 

power supply before beginning wiring, or making wiring 

connections, to prevent electrical shock or equipment damage.

!

CAUTION

Equipment Damage Hazard

Electrostatic discharge can short equipment circuitry. Ensure 

that you are properly grounded before handling the unit.

!

Economizer

Package

Unit Chassis

48/50TC

48/50HC

48/50LC

50TCQ

48/50HCQ

Carrier

Bryant

ICP

Carrier

Bryant

ICP

Carrier

Carrier

Bryant

ICP

Carrier

Bryant

ICP

ECD-SRT12TA

Chassis 1

48/50TC 

A04,A05,A06,

B04,B05,B06

580J,558J 

04A,05A,06A,

04G,05G,06G

RGS,RAS

036,048,060

48/50HC A04 581J,551J 04A

RGH,RAH

036

48/50LC A04

50TCQ 

A04,A05

548J

04A,05A

RHS 

036, 048

50HCQ A04 549J 04A RHH 036

Chassis 2

48/50TC 

A07,B07

580J,558J

07A,07G

RGS,RAS 072

48/50HC 

A05,A06

581J,551J

05A,06A

RGH,RAH

048,060

48/50LC 

A05,A06

50TCQ

A06,A07

548J

06A,07A

RHS

060,072

50HCQ

A05,A06

549J

05A,06A

RHH

048,060

ECD-SRT34TA

Chassis 3

48/50TC

A08,D08

580J,558J

08A,08D

RGS,RAS

090,091

48/50HC A07

581J,551J

07A

RGH,RAH

072

N/A

N/A

N/A

N/A

50HCQ A07 549J 07A RHH 072

Chassis 4a

48/50TC

A09,A12,

D09,D12,D14

580J,558J

09A,12A,

09D,12D,14D

RGS,RAS

101,102,121

120,150

48/50HC

D08,D09 

581J,551J

09D,12D

RGH,RAH

090,120

48/50LC 07

50TCQ

D08,D09,D12

548J

08D,09D,12D

RHS

090,102,120

50HCQ 

D08,D09

549J

08D,09D

RHH

090,102

Chassis 4b

ECD-SRT05TA

Chassis 5

48/50TC D16 580J,558J 16D RGS,RAS 180 48/50HC D14 581J,551J 14D RGH,RAH 150

48/50LC 

08,09,12

N/A

N/A

N/A

N/A

N/A

N/A

Chassis 5

N/A

N/A

N/A

N/A

N/A

N/A

N/A

50TCQ D14

548J 14D

RHS 150

50HCQ D12 549J 12D RHH 120

Base Chasis/Curb Design (3-23 ton)

GENERAL (When ordered with controls)

The system utilizes the latest technology available for integrating 

the use of free cooling with mechanical cooling for packaged 

rooftop units. The solid-state control system optimizes energy 

consumption, zone comfort, and equipment cycling by operating 

the compressors when the outdoor-air temperature is too warm, 

integrating the compressor with outdoor air when free cooling 

is available, and locking out the compressor when outdoor-air 

temperature is too cold. Demand control ventilation is supported. 
This can be used with single or multiple speed indoor fans.
The MicroMetl Ultra Low Leak Economizer utilizes gear-driven 

technology with a direct-mount spring return actuator that will close 

upon loss of power. When ordering with controls, The Ultra Low 

Leak Economizer comes standard with a Mixed Air Sensor (Also 

called The Supply Air Temperature Sensor), and the option of 

Adjustable Dry Bulb, Enthalpy, Differential Adjustable Dry Bulb, and 

Differential Enthalpy Sensors. CO2 and Smoke Detectors Sensor 

are an additional field installed option.

Table 1

*QR Code

Summary of Contents for ECD-SRT05TA-D2 Series

Page 1: ...d Electrostatic discharge can short equipment circuitry Ensure that you are properly grounded before handling the unit Economizer Package Unit Chassis 48 50TC 48 50HC 48 50LC 50TCQ 48 50HCQ Carrier Bryant ICP Carrier Bryant ICP Carrier Carrier Bryant ICP Carrier Bryant ICP ECD SRT12TA Chassis 1 48 50TC A04 A05 A06 B04 B05 B06 580J 558J 04A 05A 06A 04G 05G 06G RGS RAS 036 048 060 48 50HC A04 581J 5...

Page 2: ...pin jumper plug from the unit wiring harness located in the upper left corner of the unit Insert the Ultra Low Leak Economizer plug into the unit wiring harness Refer to Fig 9 and 10A for wiring details Fig 1 Component Locations Small Economizer Shown WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury and or death Disconnect power supply and install lock...

Page 3: ...ng of all outside dampers Warning Any circumstance which involves emergency shutdown should be carefully studied and written into company policy Please adhere to all applicable electrical local and fire emergency codes before integrating emergency devices into your HVAC scheme We recommend the MicroMetl 9901 0091 Smoke Detector Optional Power Exhaust MicroMetl carries a large variety of Power Exha...

Page 4: ...ECD SRT12TA D2 33 37 17 43 19 05 29 5 55 lb ECD SRT34TA D2 40 37 22 28 24 48 36 27 80lb ECD SRT05TA D2 52 92 27 03 33 41 49 92 98lb NOTE The ECD SRT05TA D2 Series hood has 2 aluminum filters and a hood filter divider installed between the filters See Fig 6A Fig 7 Ultra Low Leak Economizer Installed in HVAC Unit Fig 6A Hood for Extra Large Cabinet Hood Filter Divider HVAC Unit Filters Insert Screw ...

Page 5: ...unt the sensor in the indoor fan section of the unit see Figure 12 Locate the orange and brown wires in the wire bundle in the indoor fan section Connect these orange and brown wires to the 2 wire harness attached to the Sensor Mixed air default setting is 53 F and can be adjusted from 38 F to 70 F 13 While everything is open install and wire any other accessories and or sensors as applicable and ...

Page 6: ...6 Fig 10A Typical Wiring Diagram For 1 and 2 Speed Units 2 Speed Diagram Shown If using the OA enthalpy accessory the OAT must be removed Set sensor dip switches See Table 11 48TMHSRSE A20 Harness ...

Page 7: ...ts 48 50LC 07 12 See 3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of harness which is provided with 48 50LC 07 12 3 speed units 2 Harness which is provided with economizer accessory is not used on 3 speed units ...

Page 8: ...8 Fig 10C 48LCHSRADH A00 Harness for 3 Speed Units 48 50LC 07 12 Provided with 3 Speed Units FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TERMINAL BOARD ...

Page 9: ...m in the currently displayed menu 3 Use the and buttons to scroll to the desired parameter 4 Press the Enter button to display the value of the currently displayed item 5 Press the button to increase change the displayed parameter value 6 Press the button to decrease change the displayed parameter value NOTE When values are displayed pressing and holding the or button causes the display to automat...

Page 10: ...ge DA TEMP _ _ _o F 40 F to 150 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _o F if sensor sends invalid value if not con nected short or out of range OA TEMP _ _ _o F 40 to 140o F Displays measured value of outdoor air temperature Displays _ _ _o F if sensor sends invalid value short or out of range OA HUM _ _ 0 to 100 Displays measur...

Page 11: ...V VENTMAX 2 8 V 2 to 10 Vdc or 100 to 9990 cfm increment by 10 Displays only if a CO2 sensor is connected Used for Vbz ventilation max cfm setpoint Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers controlled by CFM With 2 speed fan units VENTMAX L low speed fan and VENTMAX H high speed fan settings are required Default for VENTMAX L is 3 2V and VENTMAX H is 2 8V VENTMAX L 3 2 V VE...

Page 12: ...nical cooling is 2nd stage Allows three stages of cooling 1 economizer and 2 mechanical OFF no Stage 3 cooling SD DMPR POS CLO CLO or OPN Indicates shutdown signal from space thermostat or unitary controller When controller receives 24 Vac input on the SD terminal in conventional mode the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO All other controls e ...

Page 13: ... actuator if damper is moveable and supply voltage is between 21 6 V and 26 4 V Check actuato count on STATUS menu FREEZE ALARM n a n a Check if outsoor temperature is below the LOW Temp Lockout on setpoint menu Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced menu When conditions are back in normal range then the alarm will go away SHUTDOWN ACTIVE n a n a AUX2 IN...

Page 14: ...Each Status item displays in turn and cycles to the next item after 5 seconds Label Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity insensitive connections OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor Polarity insensitive connection S BUS S BUS S BUS Sylk Bus Enthalpy Control Sensor Polarity insensitive connection Bottom Left Termina...

Page 15: ...ceeds 69 F Differential Dry Bulb 1 3 5 11 16 Outdoor air temperature exceeds return air temperature 2 4 10 Outdoor air temperature exceeds return air temperature minus 2 F 6 8 9 Outdoor air temperature exceeds return air temperature minus 4 F 7 Outdoor air temperature exceeds return air temperature minus 6 F Fixed Enthalpyb Fixed Dry Bulb All Outdoor air enthalpy exceeds 28 Btu lb of dry airb or O...

Page 16: ...gized and HL high limit when a compressor stage is energized Table 10 provided the values for each boundary limit Enthalpy control Sensor Configuration The optional Enthalpy Control sensor Part Number communicates with the W7220 Economizer controller on the two wire communications bus and can either be wired using a two pin header or using a side connector This sensor is used for OA enthalpy and r...

Page 17: ...r fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as the dampers open above the EXH1 SET setpoint and will be energized as the dampers close below the EXH1 SET setpoint Damper movement from full closed to full open or vice versa will take between 1 1 2 and 2 1 2 minutes Heating with Ultra Low Leak Economize...

Page 18: ... the temperature of air that you want to supply to the space In a commercial building this is between 50 to 55o F 10 to 13o C The mixed are is the mixing of the return air and the outdoor air I am using enthalpy sensors Why did the control ask me to input a dry bulb changeover temperature In the even the humidity sensor in the enthalpy sensors fails the backup algorithm in the control is to defaul...

Reviews: