Specifications
Table 3-43 Skylight actuator technical specifications
Item
Specifications
Power input
● DC input: terminal, with an input voltage of 36 V DC–60 V
DC
● PoE power supply: one PoE port that complies with
IEEE802.3at
PoE port
FE communication with the rate of 10/100 Mbit/s
Wireless
communicatio
n
One wireless port that complies with IEEE 802.15.4, mutual
backup with FE communication
AI/DI port
Two AI/DI ports for detecting fire extinguishing linkage signals;
smoke detection signals also supported
DO output
One 12 V DC power output for controlling the skylight
magnetic lock; driving nine skylight magnetic locks
simultaneously
DI input
One DI input port for connecting to the window open button
BLINK button
● Press the button for less than 1 second to start blinking.
● Hold down the button for 1–5 seconds to search for a
network and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
Address DIP
switch
4-pin address DIP switch
E-label
Supported
Indicators
Table 3-44 Skylight actuator indicators
Indicator Color
Name
Status
Description
Power
Green Power input
status
indicator
Steady on
The power input is normal.
Off
There is no power input.
RUN
Green Running
status
indicator
Off
The power is abnormal or
the board program is
loading.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3 Device Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
51