Path
Parameter
Setting
Connect To
Select ECC800 from the drop-down list
box.
NOTE
If the other end of the straight-through cable is
connected to the COM port on the UIM20A,
select UIM.
Communicati
ons Port
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
TP48202B is connected to the COM1 port on
the ECC800-Pro. If the TP48202B is connected
to another port, enter the number of the
connected port.
Device
Address
In this example, Device Address is set to
160. During actual configuration, set the
device address for the DC PDC based on
the actual situation.
3. Click Test Connect to check whether the DC PDC is properly connected to the
ECC800-Pro.
–
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
----End
8.1.7.11 How Can I Set and Add a SmartLi (Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
SmartLi and the other end has been connected to the PoE port on the smart ETH
gateway.
Procedure
Step 1 Set SmartLi monitoring parameters.
1. On the home screen of the SmartLi, tap System Info.
2. Choose System Info > Settings, enter the user name admin and password
000001, and tap
.
3. Tap Communication to set IP address assign to Automatic(DHCP) on the
displayed communication settings screen and the SmartLi is discovered by
ECC800-Pro automatically and is connected to the ECC800-Pro.
----End
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
274