Table 5-7 Access authorization
Access authorization
Description
Access authorization fails and the
aisle door cannot be opened.
Red light, blinking for 3 seconds
Access authorization succeeds and
the door can be opened.
Green light, blinking for 3 seconds
NO TE
– The eLight actuator is automatically associated with the nearest access actuator in the
smart module view.
– If there are one access actuator and two eLight actuators in an aisle, the access
actuator is automatically associated with the two eLight actuators.
----End
Follow-up Procedure
To modify the parameters of a single eLight, do as follows:
1. Choose Monitoring > Aisle > eLight Actuator Group > eLight Actuator. The
Running Parameters page is displayed.
2. Select the Associated alarm severity as required and click Submit.
Table 5-8 Function commissioning
Item
Alarm Severity
Selection
Description
Associated
alarm severity
Critical
If there is a critical alarm, the
eLight strip light turns on with a
red light.
Critical, Major
If there are multiple alarms, the
eLight strip light preferentially
turns on with a light
corresponding to the high-
severity alarm. After the high-
severity alarm is cleared, the
eLight strip light turns on with a
light corresponding to the low-
severity alarm.
NOTE
● Critical: red light
● Major: orange light
● Minor: yellow light
● Warning: white light
Critical, Major,
Minor
Critical, Major,
Minor, Warning
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
5 Power-On Commissioning
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
117