Path
Parameter
Setting
Communicati
ons Port
Select COM2 from the drop-down list box.
NOTE
The setting example indicates that the Envicool
IFX Terminal is connected to the COM2 port on
the ECC800-Pro. If the Envicool IFX Terminal is
connected to another port, enter the number of
the connected port.
Device
Address
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the air conditioner based on
the actual situation.
3. Click Test Connect to check whether the Envicool air conditioner is properly
connected to the ECC800-Pro.
–
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
----End
8.1.7.10 How Can I Set and Add a TP48202B (Modbus-RTU)?
Prerequisites
One end of the straight-through cable has been connected to the RS485/RS232
port on the power distribution monitoring unit in the DC PDC, and the other end
has been connected to the COM port on the ECC800-Pro collector or UIM20A.
Procedure
Step 1 Add a TP48202B (Modbus-RTU).
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a TP48202B.
Table 8-10 Adding a TP48202B
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device.
Device
Attribute
Select PDU from the drop-down list box.
Device Type
Select TP48202BDCEndCabinet from the
drop-down list box.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ