Path
Parameter
Setting
Device
Address
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the PDU8000 based on the
actual situation.
3. Click Test Connect to check whether the PDU8000 connects to the ECC800-
Pro properly.
–
If the PDU8000 connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.
–
If the connection fails, check whether the PDU8000 is properly connected
to the ECC800-Pro, whether the PDU8000 and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
PDU8000 parameters.
----End
8.1.7.14 How Can I Set and Add a 5G DC Power Supply (Modbus-RTU)?
Prerequisites
One end of the straight-through cable has been connected to the RS485 port on
the SMU02C in the MTS9604B-N20B1 cabinet, and the other end has been
connected to the COM port on the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Connect the RS485 communications port on the SMU02C.
Figure 8-12 RS485 communications port
Step 2 Add a 5G DC power supply.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a 5G DC power supply.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
277