HDG Bavaria GmbH 07/2008
HDG Compact 99 - 200 - Version 1 - en
6 Using the heating system – TIME menu
95
S
ETTING
THE
FILLING
,
IGNITION
AND
FAN
ACTIVATION
This submenu is used to set the time for the initial filling with fuel and
the running time of the ignition fan. You can also set the time after
which the combustion fan is added during the igniting phase.
✎
See “Procedure” in this section.
S
ETTING
PRE
-
AIR
,
HEATING
UP
AND
BURNING
OUT
This submenu enables you to set the pre-ventilation time for fanning
the fuel without material feeding, the heating up time during which
the fuel quantity is heated to the target value, and the burn-out time
during which material feeding is stopped and the combustion fan
switches off after a specified time.
✎
See “Procedure” in this section.
S
ETTING
THE
ASH
REMOVAL
AND
EMBER
SUSTAINING
FUNCTIONS
This submenu is used to set the time for the grate motion and thus
the de-ashing interval. In addition, the time interval for the material
feeding can be influenced if the
Ignition
parameter is set to
Off
.
✎
See “Procedure” in this section.
Time
3-01
1st filling
:
6.0 / 0.0 m
Ignition
:
6.0 / 0.0 m
Fan activation
:
3.0 / 0.0 m
END
When changing the fuel, the parameters
1st filling
and
Ig-
nition
must be regulated to avoid malfunctions during ignition.
Time 3-02
Pre-ventilation
: 30
/ 0
s
Heating up
:
7.0 / 0.0 m
Burning out
: 30.0 / 0.0 m
END
The
Keep glow
setting is only used as an “emergency” function
should the ignition fan fail!