6 Using the heating system – Performing the chimney sweep test
120
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
T
EST
EVERY
TWO
YEARS
In Germany, regular inspections every two years must be carried out
in accordance with the requirements of the federal emission limits
(1. BImschV).
B
EFORE
THE
TEST
1.
Clean the heating system completely about 2-3 days prior to the
test.
✎
See the chapter entitled “7 Cleaning and servicing the heating
system”, section “7.1 Cleaning and maintenance schedule”.
2.
Check that the lambda sensor is securely mounted and tighten it
if necessary.
✎
See the chapter entitled “7 Cleaning and servicing the heating
system”, section “7.1 Cleaning and maintenance schedule”.
D
URING
THE
TEST
Please observe the following when carrying out the chimney sweep
test:
•
Make sure that there is sufficient fuel in the fuel bunker to avoid in-
terruption of material feeding during the measurement.
•
No fault should be present in the system.
1.
Press the
F5
key under the standard display screen.
✓
You are in the
Service
menu.
Warning!
Material damage and injury due to incorrect chimney sweep test
The chimney sweep test requires comprehensive technical know-
ledge.
Only permit authorised specialists to perform the chimney sweep
test.
At the start of the measurement, the boiler temperature should not
exceed 75 °C. If there is an accumulator, its temperature should not
exceed 60°C. Ensure there is sufficient heating demand placed on
the heating circuit.
The chimney sweep measurement must be performed when opera-
ting at full load. (It is absolutely essential to avoid the heating up
and burning out phases.) Having the measurement repeated by the
combustion engineer or by HDG specialists will incur charges.