6 Using the heating system – SERVICE menu
108
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
C
HIMNEY
SWEEP
TEST
•
30%
– Starts the partial load measurement
•
100%
– Starts the partial load measurement
1.
Press the
F5
key under the display of the standard display screen.
✓
You are in the
SERVICE
menu.
✓
The display changes to the
Service 5-01
submenu.
2.
Press the
F4
key under the “Chimney sweep inspection” symbol.
3.
Press the
F3
or
F4
key to start the chimney sweep test.
✓
The chimney sweep test is carried out.
O
PERATING
HOURS
COUNTER
Various operating hours are displayed. Pressing the
RESET
key for
more than 3 seconds resets all operating hours.
✎
See “Procedure” in this section.
When operating the heating system without an accumulator, the
chimney sweep test can also be carried out in partial load mode
with 30% of the nominal thermal power.
Chimney sweep test
5-02
Temperature reached
Boiler temperature
:
48°C
Comb.chamber temp.
:
529°C
Measurement time
:
75 / 0 m
30%
100%
END
Operating hours counter
5-04
Boiler
:
0:00:00
Dosage
:
0:00:00
Feeding
:
0:00:00
Ash removal
:
0:00:00
END