HDG Bavaria GmbH 07/2008
HDG Compact 99 - 200 - Version 1 - en
6 Using the heating system – °C/QUANTITY menu
91
E
NTERING
MATERIAL
AND
TEMPERATURE
SETTINGS
In this menu, you can define the fuel quantity for controlled opera-
tion of the boiler. The furnace temperature setting is also set for the
control type “Combustion control”.
✎
See “Procedure” in this section.
E
NTERING
THE
PRIMARY
AIR
SETTING
In this menu, you can set the primary air quantity for controlled ope-
ration of the boiler.
✎
See “Procedure” in this section.
The standard setting is
MAX
600°C and
MIN
400°C.
The material settings apply for
Combustion control
as well as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation, ignition and Lambda Stop”.
Material quantity
PID-2
6-02
MAX: 28.0%
CCT_SET: 600°C
KP:
5.00
MIN:
15.0%
CCT_ACT: 50°C TN: 100.00
TV: 0.00
SET: 15.0%
Factor :
50%
KP_
17.90
END
The difference between fuel quantity
MAX
and
MIN
should be spe-
cified as a range (approx. 25%) adapting to the required value.
The primary air settings apply for
Combustion control
as well
as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation, ignition and Lambda Stop”.
Primary air
R-1
6-03
Air_Max
: 30%
Fue_Set:
15.0%
Air_Min
: 25%
Set_Air: 25.0%
END