8 Troubleshooting – Possible faults
154
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
WA210
Lambda sensor
Heating element
faulty
•
Heating element of lambda
sensor faulty
•
Lambda probe faulty
•
Relay in control cabinet
faulty
•
Fuse F12 blown
•
Check the electrical connec-
tion
•
Replace lambda probe
•
Replace relay
•
Unlock automatic circuit
breaker F12
WA211
Lambda sensor
check
•
Heating element of lambda
sensor faulty
•
Lambda probe faulty
•
Analogue module faulty
•
Check the electrical connec-
tion
•
Replace lambda probe
•
Check analogue module
WA212
Lambda probe
faulty
•
Heating element of lambda
sensor faulty
•
Lambda probe faulty
•
Analogue module faulty
•
Check the electrical connec-
tion
•
Replace lambda probe
•
Check analogue module
WA213
Check pellet
vacuum contai-
ner filling
level
•
Pellet storage space empty
•
Check pellet storage space
and fill if necessary
WA215
Delay at antic-
lockwise hose
junction
•
Hose junction blocked
•
Faulty reference limit switch
•
Fuse triggered
•
Motor incorrectly connected
•
Motor overload
•
Motor is faulty
•
Motor cable faulty
•
Check hose junction
•
Check reference limit switch
•
Check fuse
•
Check the motor connection
•
Check the drive
•
Check the motor
•
Check the motor cable
WA216
Delay at clock-
wise hose junc-
tion
•
Hose junction blocked
•
Faulty reference limit switch
•
Fuse triggered
•
Motor incorrectly connected
•
Motor overload
•
Motor is faulty
•
Motor cable faulty
•
Check hose junction
•
Check position limit switch
•
Check fuse
•
Check the motor connection
•
Check the drive
•
Check the motor
•
Check the motor cable
WA217
Moving floor
approval mis-
sing
•
Switch in control cabinet not
switched on
•
Fault not acknowledged
•
Switch on the switch in the
control cabinet
•
Acknowledge fault
WA218
The moving floor
is switched off
•
Information on moving floor
activity
WA219
Check pellet
storage space 1
filling level
•
Pellet storage space 1 empty
•
Check pellet storage space 1
and fill if necessary
WA220
Check pellet
storage space 2
filling level
•
Pellet storage space 2 empty
•
Check pellet storage space 2
and fill if necessary
No.
Fault
Cause
Remedy
Table 8/1 - Faults (continuation)