HDG Bavaria GmbH 07/2008
HDG Compact 99 - 200 - Version 1 - en
6 Using the heating system – SERVICE menu
115
•
Boiler set temperature 30/100%
– The boiler set temperature for the chimney sweep test in par-
tial load (30%) and nominal load (100%) can be set.
•
Combustion chamber set temperature 30/100%
– The combustion set temperature for the chimney sweep test in
partial load (30%) and nominal load (100%) can be set.
✎
See “Procedure” in this section.
S
ETTING
INTERFACE
RS485
•
Interface RS485
Setting options:
– without interface
– Modbus RTU web server
– Modbus RTU DDC
– Profibus DP DDC
✎
See “Procedure” in this section.
Chimney sweep test
5-15
Enabling boiler temperature
: 70 / 60 °C
Enabling combustion room temp.: 450 / 328 °C
Boiler temp. Set 30/100%
:
85 / 85 °C
Set comb. chamber temp. 30/100% :480/ 570 °C
END
Setting interface RS485
5-16
Interface type
:without interface
FIELD
END