6 Using the heating system – °C/QUANTITY menu
87
S
ETTING
THE
BOILER
SUPPLY
AND
RETURN
TEMPERATURE
✎
See “Procedure” in this section.
R
EADING
VALUES
FROM
THE
CONTROLLER
You can read off the relevant values in the display.
✎
See “Procedure” in this section.
F
IXED
VALUE
- S
ETTING
THE
MATERIAL
AND
AIR
QUANTITY
✎
See “Procedure” in this section.
°C /
Quantity
2-02
Boiler temp.
:
80 /
60 °C
Return temp.
:
60 /
50 °C
Comb. chamber temp.
: 600 / 331 °C
Residual oxygen
: 8.0 /8.6 %
END
The
Boiler temperature
target value must not fall below 70°C
and must not exceed 85°C. The
Return temperature
target
value must not fall below 60°C.
Comb. chamber temp.
and
Re-
sidual oxygen
cannot be changed!
Values from controller
2-03
Material quantity
: 50.0 /.40.0 %
Material difference
:
.0 /50.0 %
Primary air
:
25 /
1 %
Secondary air
:
20 /
1 %
END
Fixed value settings
2-04
Material quantity
: 40.0 /.40.0 %
Primary air
:
15 /
1 %
Secondary air
:
80 /
1 %
Comb. chamber temp.
:
600 / 331 °C
END