6 Using the heating system – SERVICE menu
110
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
S
ETTING
THE
BOILER
OVERHEATING
TEMPERATURE
OR
HYSTERESIS
,
MINIMUM
RETURN
TEMPERATURE
AND
COMBUSTION
CHAMBER
STOP
TEMPERATURE
•
Boiler overheat temperature
– When the set boiler temperature is exceeded by this set value,
the boiler shuts off.
•
Boiler temperature hysteresis
– The boiler temperature hysteresis is used to set a temperature
difference between the temperature at which the heating
system is switched on and the temperature at which it is swit-
ched off (only for “Boiler activation on”).
•
Minimum return temperature
– Set the minimum return temperature. This limits the minimum
value of the return temperature in parameter
2-02
.
•
Combustion chamber temperature stop
– After the set temperature is exceeded, the heating system swit-
ches to the operating state Combustion chamber temperature
stop.
✎
See “Procedure” in this section.
M
ODIFYING
THE
DOSAGE
PAUSE
MIN
.
OR
IMPULSE
MIN
.
AND
FEED
SYSTEM
LAG
TIME
OR
FEED
SYSTEM
LEAD
TIME
PARAMETERS
•
Dosage pause min. and dosage impulse min.
– These parameters are used to set the minimum pause intervals
and running time of the extraction for the fuel metering.
•
Feed system lag time
– This parameter determines the lag time of the rotary feeder
and the stoker auger. The continued running empties the
auger channel when the heating system is shut off.
•
Feeding system lead time
– After a prior Lambda stop, combustion chamber temperature
stop or material stop, the feed system starts early by the
amount of the set value.
Service
5-06
Boiler temp. Overheating
:
5 °C
Boiler temperature hysteresis:
2 °C
Minimum return temperature:
60 °C
Combustion chamber temp. stop
:
750 °C
END