Parameter
Units
Minimum
Maximum
Default
PSIG
60.3 PSIG
335.3 PSIG
335.3 PSIG
PSIA
75.0 PSIA
350.0 PSIA
350.0 PSIA
kPaG
416 kPaG
2312 kPaG
2312 kPaG
kPaA
517 kPaA
2413 kPaA
2413 kPaA
MPaG
0.416 MPaG
2.312 MPaG
2.312 MPaG
MPaA
0.517 MPaA
2.413 MPaA
2.413 MPaA
kg/cm²G
4.24 kg/cm²G
23.58 kg/cm²G
23.58 kg/cm²G
kg/cm²A
5.27 kg/cm²A
24.61 kg/cm²A
24.61 kg/cm²A
Water Pump Lockout Next Device
Delay
Minutes
1 min
30 min
1 min
Water Pump Lockout Previous
Device Delay
Minutes
1 min
30 min
1 min
1.
Water Pump Lockout Enabled
This parameter is used to select whether the condenser water pumps are configured to become locked out
below a selected temperature value. The options are:
•
Disabled
•
Enabled
2.
Water Pump Lockout Start
This parameter is used to select the ambient temperature value below which the water pumps will be locked
out. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
3.
Water Pump Lockout End
This parameter is used to select the value that the ambient temperature must rise above after the pumps
have become locked out before they will be permitted to resume normal operation. The value is measured in
the panel temperature units as selected on the
Panel Settings
screen.
4.
Water Pump Lockout Discharge Pressure Override Start
This parameter is used to select the condenser discharge pressure above whichthe water pump lockout will
be overridden. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
5.
Water Pump Lockout Discharge Pressure Override End
This parameter is used to select the value that the discharge pressure of the condenser must fall below after
the water pump lockout has been overridden before the override will end. The value is measured in the
panel pressure units as selected on the
Panel Settings
screen.
Control
Condenser Sequencer Control Parameters
Instruction Manual | GEA Omni™
Control panel
162
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016