3.1.20
Inlet Temperature
Parameter
Units
Minimum
Maximum
Default
High Inlet Temperature Warning
°C
-75.0 °C
100.0 °C
100.0 °C
°F
-103.0 °F
212.0 °F
212.0 °F
Low Inlet Temperature Warning
°C
-75.0 °C
100.0 °C
-28.9 K
°F
-103.0 °F
212.0 °F
-20.0 F°
1.
High Inlet Temperature Warning
This parameter is used to select the value of the inlet oil temperature above which a
High Inlet Temperature
Warning
condition will be annunciated. The parameter will only be visible if the control signal of the compres-
sor is currently set to
Inlet Temperature
. The value is measured in the current temperature units of the panel
as selected on the
Panel Settings
screen.
2.
Low Inlet Temperature Warning
This parameter is used to select the value of the inlet oil temperature below which a
Low Inlet Temperature
Warning
condition will be annunciated. The parameter will only be visible if the control signal of the compres-
sor is currently set to
Inlet Temperature
. The value is measured in the current temperature units of the panel
as selected on the
Panel Settings
screen.
3.1.21
Outlet Temperature
Parameter
Units
Minimum
Maximum
Default
High Outlet Temperature Warning
°C
-75.0 °C
100.0 °C
100.0 °C
°F
-103.0 °F
212.0 °F
212.0 °F
High Outlet Temperature Warning
Timer
Seconds
0 s
300 s
120 s
Low Outlet Temperature Shutdown
°C
-60.0 °C
200.0 °C
28.9 °C
°F
-76.0 °F
392.0 °F
84.0 °C
Low Outlet Temperature Shutdown
Timer
Seconds
0 s
300 s
120 s
Low Outlet Temperature Warning
Offset
Kelvin
0.0 K
50.0 K
5.0 K
°F
32.0 °F
122.0 °F
41.0 °F
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
145
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......