Warning
Explanation
Illegal Oil Filter Differential
Pressure Warning
This annunciation will be triggered if the calculated value of the
Oil Filter Dif-
ferential
falls below -2 PSID.
Oil Pump Loss of Interlock Aux-
iliary 1 Warning
This annunciation will be triggered if the interlock input of the lead oil pump in
a dual pump system becomes de-energized while the pump is supposed to
be running. This annunciation will only be enabled if the compressor is con-
figured with dual oil pumps, and the first pump is selected as the lead pump.
An annunciation will cause the lag pump to start.
Oil Pump Loss of Interlock Aux-
iliary 2 Warning
This annunciation will be triggered if the interlock input of the lead oil pump in
a dual pump system becomes de-energized while the pump is supposed to
be running. This annunciation will only be enabled if the compressor is con-
figured with dual oil pumps, and the second pump is selected as the lead
pump. An annunciation will cause the lag pump to start.
Low Suction Pressure Warning
This annunciation will be triggered if the compressor suction pressure
exceeds the value obtained by subtracting the
Low Suction Pressure Warn-
ing Offset’
parameter from the
Low Suction Pressure Shutdown
parameter.
High Inlet Temperature Warn-
ing
This annunciation will be triggered if the inlet temperature reading exceeds
the value of the
High Inlet Temperature Warning
parameter.
Low Inlet Temperature Warning This annunciation will be triggered if the inlet temperature reading falls below
the value of the
Low Inlet Temperature Warning
parameter.
High Outlet Temperature Warn-
ing
This annunciation will be triggered if the outlet temperature reading exceeds
the value of the
High Outlet Temperature Warning
parameter.
Low Outlet Temperature Warn-
ing
This annunciation will be triggered if the outlet temperature reading falls
below the value of the
Low Outlet Temperature Warning
parameter.
High Oil Differential Pressure
Warning
This annunciation will be triggered if the calculated oil differential pressure
exceeds the value obtained by subtracting the
High Oil Differential Pressure
Warning Offset
parameter from the
High Oil Differential Pressure Shutdown
parameter.
Low Oil Differential Pressure
Warning
This annunciation will be triggered if the calculated oil differential pressure
falls below the value obtained by adding the
Low Oil Differential Pressure
Warning Offset
parameter to the
Low Oil Differential Pressure Shutdown
parameter.
Annunciations
Warnings
Instruction Manual | GEA Omni™
Control panel
216
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016