2.
High Discharge Pressure Booster Shutdown
This parameter is used to select the suction pressure value above which a
High Discharge Pressure Shut-
down
will be annunciated. The parameter will only appear if the compressor application is set to
Swing
in the
configuration. The shutdown will only be issued if the compressor currently operating as a booster. The
value is measured in the panel pressure units as selected on the
Panel Settings
screen.
3.
High Discharge Pressure High Stage Shutdown
This parameter is used to select the suction pressure value above which a
High Discharge Pressure Shut-
down
will be annunciated. The parameter will only appear if the compressor application is set to
Swing
in the
configuration. The shutdown will only be issued if the compressor currently operating as a high stage. The
value is measured in the panel pressure units as selected on the
Panel Settings
screen.
4.
High Discharge Pressure Warning Offset
This parameter is used to set an offset value subtracted from the
High Discharge Pressure Shutdown
parameter. If the discharge pressure exceeds this calculated value, a
High Discharge Pressure Warning
will
be annunciated. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
5.
Limitation Discharge Pressure Load Inhibit Offset
This parameter is used to set an offset value subtracted from the
Low Discharge Pressure Shutdown
param-
eter. If the discharge pressure rises above this calculated value, the compressor will be prevented from load-
ing. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
6.
Limitation Discharge Pressure Force Unload Offset
This parameter is used to set an offset value subtracted from the
Low Discharge Pressure Shutdown
param-
eter. If the discharge pressure rises above this calculated value, the compressor will be forced to unload.
The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
3.1.18
Discharge Temperature
Parameter
Units
Minimum
Maximum
Default
High Discharge Temperature Shut-
down
°C
1.0 °C
200.0 °C
100.0 °C
°F
33.8 °F
392.0 °F
212.0 °F
High Discharge Temperature Warn-
ing Offset
Kelvin
0.0 K
50.0 K
4.4 K
F°
0.0 F°
90.0 F°
8.0 F°
1.
High Discharge Temperature Shutdown
This parameter is used to select the discharge temperature value above which a
High Discharge Tempera-
ture Shutdown
will be annunciated. The shutdown will only be issued if the compressor is running. The value
is measured in the panel temperature units as selected on the
Panel Settings
screen.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
142
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016