2.14.2
Sensors Tab
fig.97:
Sensors tab display
This tab is used to adjust the range of sensors monitored by the panel. The table is divided into nine columns.
The leftmost column contains an icon that indicates whether the chosen point is an input or output. A green
arrow pointing to the right indicates that the point is an input, and a blue arrow pointing to the left indicates that
the point is an output. The remaining channels are detailed below.
1.
Channel
The text in this column indicates the slice number and channel that the chosen point occupies in the I/O sys-
tem.
2.
Description
This column contains the name of the chosen point.
3.
Min
This column contains the lowest allowable value for the chosen point during normal panel operation.
4.
Measured
This column contains the calibrated value read from or transmitted to the chosen point.
5.
Max
This column contains the highest allowable value for the chosen point during normal panel operation.
6.
Raw Scaled
This column contains the
Raw Signal
received by associated sensor scaled between the selected minimum
and maximum values.
7.
Offset
This column contains the value that is added to the reading displayed in the
Raw Scaled
column to obtain
the measured value for the sensor.
8.
Raw Signal
This column contains the unscaled value received by the sensor.
User interface
Configuration
Instruction Manual | GEA Omni™
Control panel
96
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016