2.
High Discharge Temperature Warning Offset
This parameter is used to set an offset subtracted from the
High Discharge Temperature Shutdown
parame-
ter. If the discharge temperature exceeds this calculated value, a
High Discharge Temperature Warning
will
be annunciated. The warning will only be issued if the compressor is running. The value is measured in the
panel temperature units as selected on the
Panel Settings
screen.
3.1.19
Oil Cooling
Parameter
Units
Minimum
Maximum
Default
Oil Cooling Control Signal
Selection – See Description
Motorized Liquid Injection Valve
Temperature Set Point
°C
45.0 °C
80.0 °C
65.0 °C
°F
113.0 °F
176.00 °F
149.0 °F
Minimum Valve Position
Percent
2%
100%
10%
Proportional Term
Unitless
0
500
250
Integral Term
s/R
1.0 s/R
250.0 s/R
40.0 s/R
Mode
Selection – See Description
Manual Mode Position
Percent
0%
100%
0%
Calibrate Time Before Bleed
Seconds
5 s
90 s
30 s
Liquid Injection Begin
°C
0.0 °C
140.0 °C
54.4 °C
°F
32.0°F
284.0 °F
130 °F
Liquid Injection End
°C
0.0 °C
140.0 °C
48.9 °C
°F
32.0°F
284.0 °F
120 °F
Liquid Injection Pulse Period
Seconds
4 s
30 s
4 s
1.
Oil Cooling Control Signal
This parameter is used to select which temperature value will be referenced for control of the oil cooling sol-
enoid. The options are:
•
Discharge Temperature
•
Inlet Oil Temperature
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
143