Parameter
Units
Minimum
Maximum
Default
Motor Stop to Start Delay
Seconds
1 s
60 s
5 s
Motor Bypass Configuration
Selection – See Description
Motor Bypass Configuration By
Digital Input
Selection – See Description
1.
Accumulated Runtime Hours
This parameter displays the total amount of time the motor has been in the run state. It may also be changed
manually. The value is measured in hours.
2.
Motor Start To Start Delay
This parameter is used to select the period of time that must elapse after the motor starts before it will be
permitted to start again. The value is measured in minutes.
3.
Motor Stop To Start Delay
This parameter is used to select the period of time that must elapse after the motor has stopped before it will
be permitted to start again. The value is measured in seconds.
4.
Motor Bypass Configuration
This parameter is used to select the whether the motor will operate as a variable speed or fixed speed motor
while it is operating in bypass mode. The parameter is only visible if the motor type is set to
Variable Speed
with Bypass
in the configuration and the
Motor Bypass Configuration by Digital Input
parameter is currently
set to
Disabled
. The options are:
•
Fixed Speed
•
Variable Speed
5.
Motor Bypass Configuration By Digital Input
This parameter is used to select whether the operating mode of the motor bypass is controlled by a digital
input. The parameter is only visible if the motor type is set to
Variable Speed with Bypass
in the configura-
tion. The options are:
•
Disabled
•
Enabled
3.1.5
Motor Power
Parameter
Units
Minimum
Maximum
Default
kW Demand Metering Ratio
kW
0.0 kW
3200.0 KW
0.0 kW
kWh Input Pulse Weight
kWh Estimated Usage
kWh
0.0 kWh
10 x 10
9
kWh
0.0 kWh
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
115