13.
Oil Pump Circulation Mode
This parameter is used to select the mode of operation of the oil circulation system, if applicable. The options
are:
•
Disabled
This option indicates that the panel is not configured to control oil circulation.
•
Temperature
This option indicates that when the compressor is starting, the panel will check that the oil temperature is
greater than or equal to the value of the
Oil Pump Circulation Temperature Set Point
. If the oil tempera-
ture does not meet this condition, the oil pump will run to attempt to bring the temperature reading up to
the appropriate value. If the temperature has not reached the selected value after a period of time speci-
fied in the
Oil Pump Circulation Shutdown Timer
parameter, a shutdown will be annunciated.
•
Time
This option indicates that whenever the compressor is in the stopped state, the oil pump will periodically
run for a period of time determined in the
Duration of Oil Pump Circulation
parameter. The time that will
elapse between circulation cycles is selected in the
Time Between Oil Pump Circulation
parameter.
14.
Oil Pump Circulation Temperature Set Point
This parameter is used to select the value that the oil temperature must exceed on startup. If the oil tempera-
ture is below this set point, the oil pump circulation will start. This parameter is only visible if the
Oil Pump
Circulation Mode
parameter is set to
Temperature
. The value is measured in the panel temperature units as
selected in the
Panel Settings
screen.
15.
Oil Pump Circulation Shutdown Timer
This parameter is used to select the period of time that the oil pump will circulate to attempt to raise the oil
temperature to an appropriate value before a shutdown condition will be annunciated. This parameter is only
visible if the
Oil Pump Circulation Mode
parameter is set to
Temperature
. The value is measured in seconds.
16.
Time Between Oil Pump Circulation
This parameter is used to select the period of time the oil pump will be stopped between circulation cycles. It
is only visible if the
Oil Pump Circulation Mode
parameter is set to
Time
. The value is measured in hours.
17.
Duration Of Oil Pump Circulation
This parameter is used to select the period of time the oil pump will run during a circulation cycle. It is only
visible if the
Oil Pump Circulation Mode
parameter is set to
Time
. The value is measured in minutes.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
125
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......