Parameter
Units
Minimum
Maximum
Default
Low Suction Pressure Booster
Shutdown
barG
-0.91 barG
12.78 barG
-0.91 barG
barA
0.10 barA
10.00 barA
0.34 barA
PSIG
27.0 inHg
185.3 PSIG
27.0 inHg
PSIA
1.5 PSIA
200.0 PSIA
1.5 PSIA
kPaG
-91 kPaG
1278 kPaG
-91 kPaG
kPaA
10 kPaA
1379 kPaA
10 kPaA
MPaG
-0.091 MPaG
1.278 MPaG
-0.091 MPaG
MPaA
0.010 MPaA
1.379 MPaA
0.010 MPaA
kg/cm²G
684.8 mmHg
13.03 kg/cm²G
684.8 mmHg
kg/cm²A
0.10 kg/cm²A
14.06 kg/cm²A
0.10 kg/cm²A
Low Suction Pressure High Stage
Shutdown
barG
-0.91 barG
12.78 barG
-0.91 barG
barA
0.10 barA
10.00 barA
0.34 barA
PSIG
27.0 inHg
185.3 PSIG
27.0 inHg
PSIA
1.5 PSIA
200.0 PSIA
1.5 PSIA
kPaG
-91 kPaG
1278 kPaG
-91 kPaG
kPaA
10 kPaA
1379 kPaA
10 kPaA
MPaG
-0.091 MPaG
1.278 MPaG
-0.091 MPaG
MPaA
0.010 MPaA
1.379 MPaA
0.010 MPaA
kg/cm²G
684.8 mmHg
13.03 kg/cm²G
684.8 mmHg
kg/cm²A
0.10 kg/cm²A
14.06 kg/cm²A
0.10 kg/cm²A
Low Suction Pressure Warning Off-
set
barG
0.00 barD
5.00 barD
0.14 barD
barA
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
136
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni