3.
Application
This drop down list is used to select the function of the compressor. The options are:
•
Standard / High Stage
•
Booster / Low Stage
•
Swing
•
Heat Pump
4.
Brand
This drop down list is used to select the compressor’s manufacturer information.
5.
Series
This drop down list is used to select the series of the compressor. The options that will appear in this box
are dependent on the selected manufacturer.
6.
Vi Mode
This drop down list is used to select the type of variable Vi control of the compressor. The options are:
•
Fixed
•
Continuous Variable
•
Step Variable
7.
Vi Position Sensor
This drop down list is used to select the type of position sensor for monitoring the position of the VI, Vol-
ume or Secondary Slide. If the compressor is fixed Vi, the only available option will be None. This option
may not be modified in the field.
8.
Model
This drop down list is used to select the specific model number associated with the compressor. The
options that will appear in this box are dependent on the selected series and manufacturer.
Furthermore, if the selected manufacturer is Grasso, the field will be split into three separate drop-down
lists instead of one and a second drop down list will appear in the right column which. In this situation,
changes in any drop down list will trigger a matching change in the other list.
This option may only be modified in the field for certain compressor brands and series.
9.
Primary Slide Control Devices
This drop down list is used to select the type of device that will control the package’s primary capacity
slide valve. This option may only be modified in the field for certain compressor brands and series. The
options are:
•
Dual Solenoids
•
Single Solenoids
Control
Configuration
Instruction Manual | GEA Omni™
Control panel
188