Value
Description
Oil Pump Interlock
This input monitors the status of the oil pump run feedback module. It will be ener-
gized while the oil pump is running, and de-energized while the oil pump is stop-
ped. If this input ever becomes de-energized while the oil pump is running, or
energized while the oil pump is stopped, an interlock alarm condition will be trig-
gered. The states are
On
or
Off
.
External Unload
This input monitors the status of a remote compressor control device. This module
will only be used if the panel is operating in Remote Mode. It will be energized to
remotely instruct the compressor to unload, and de-energized at all other times.
The states are
On
or
Off
.
External Load
This input monitors the status of a remote compressor control device. This module
will only be used if the panel is operating in Remote Mode. It will be energized to
remotely instruct the compressor to load, and de-energized at all other times. The
states are
On
or
Off
.
External Start/Stop
This input monitors the status of a remote compressor control device. This module
will only be used if the panel is operating in Remote Mode. It will be energized to
remotely instruct the compressor to start, and de-energized to instruct it to stop.
The states are
On
or
Off
.
Start Permissive
This input monitors whether the compressor is currently allowed to start. As long
as it is energized, the compressor may start normally, otherwise any instruction to
start will be ignored. The states are
On
or
Off
.
Low Oil Level
This input monitors an oil level float switch. It will be energized for normal opera-
tion of the panel, and will only de-energize if the oil level falls below the level of the
switch. The states are
On
or
Off
.
Aux Shutdown #1
This input monitors a miscellaneous shutdown condition for the compressor. It will
be energized for normal panel operation. If this input ever becomes de-energized,
a shutdown annunciation will be triggered. The states are
On
or
Off
.
Aux Warning
This input monitors a miscellaneous warning condition for the compressor. It will
be energized for normal panel operation. If this input ever becomes de-energized,
a warning annunciation will be triggered. The states are
On
or
Off
.
Set Point Select
This input is used to control which set point is currently being used. This module
will only be enabled if the compressor is configured for multiple set points. Set
point 2 will be enabled if the module is energized, and set point 1 will be enabled if
it is de-energized. The states are
On
or
Off
.
Auxiliary Shutdown #2
This input monitors a miscellaneous shutdown condition for the compressor. It will
be energized for normal panel operation. If this input ever becomes de-energized,
a shutdown annunciation will be triggered. The states are
On
or
Off
.
Control
Compressor Operating Data
Instruction Manual | GEA Omni™
Control panel
180
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016