4.
Soft Hot Gas
This parameter is used to select whether the Soft Hot Gas solenoid output is inverted. The options are
Disa-
bled
, where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
5.
Bleed
This parameter is used to select whether the Bleed solenoid output is inverted. The options are
Disabled
,
where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
6.
Fans
This parameter is used to select whether the Fans solenoid output is inverted. The options are
Disabled
,
where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
3.5.6
Evaporator for Chiller
Parameter
Units
Minimum
Maximum
Default
Secondary Refrigerant
Secondary Refrigerant Feedback
Flow Delay
Seconds
0 s
999 s
60 s
Secondary Refrigerant Pump Stop
Delay
Seconds
0 s
999 s
5 s
Secondary Refrigerant Feedback
Pump Delay
Seconds
0 s
999 s
60 s
Liquid Feed
Set Point
Percent
0.0 %
100.0 %
18.0 %
Proportional Term
None
0.0
500.0
250.0
Integral Term
s/R
1.0 s/R
250.0 s/R
40.0 s/R
Dead Band
Percent
0.0 %
10.0 %
2.0 %
Maximum Level
Percent
0.0 %
100.0 %
50.0 %
High Level Warning Delay (Liquid
Feed Maximum Level Warning
Delay)
Seconds
0 s
60 s
5 s
High Level Shutdown Delay (Liquid
Feed Maximum Level Shutdown
Delay)
Seconds
0 s
60 s
15 s
Instruction Manual | GEA Omni™
Control panel
Control
Evaporator Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
171