6.
Superheat Discharge Annunciations
This parameter is used to select whether the panel discharge superheat calculations are configured to trig-
ger shutdown annunciations.
7.
High Discharge Superheat Shutdown
This parameter is used to select the
Discharge Superheat
temperature above which a
High Discharge
Superheat Shutdown
will be annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The shutdown will only be issued if the compressor is starting or run-
ning. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
8.
High Discharge Superheat Shutdown Timer
This parameter is used to select the period of time that the
Discharge Superheat
value must remain above
the value of the
High Discharge Superheat
parameter before a
High Discharge Superheat Shutdown
is
annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The value is measured in seconds.
9.
Low Discharge Superheat Shutdown
This parameter is used to select the
Discharge Superheat
temperature below which a
Low Discharge Super-
heat Shutdown
will be annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The shutdown will only be issued if the compressor is starting or run-
ning. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
10.
Low Discharge Superheat Shutdown Timer
This parameter is used to select the period of time that the
Discharge Superheat
value must remain below
the value of the
Low Discharge Superheat
parameter before a
Low Discharge Superheat Shutdown
is
annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The value is measured in seconds.
3.1.25
Economizer
Parameter
Units
Minimum
Maximum
Default
Economizer Output On Above
Capacity Slide
Percent
0 %
100 %
80 %
Economizer Output Off Below
Capacity Slide
Percent
0 %
100 %
70 %
1.
Economizer Output On Above Capacity Slide
This parameter is used to select the position of the capacity slide above which the economizer solenoid will
be energized. This parameter will only be visible if the economizer option in the configuration is not set to
Disabled
. The value is measured in percent.
2.
Economizer Output Off Below Capacity Slide
This parameter is used to select the position of the capacity slide below which the economizer solenoid will
be de-energized. This parameter will only be visible if the economizer option in the configuration is not set to
Disabled
. The value is measured in percent.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
150
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......