5.3.3
Calibration for Capacity Slide for Step Variable Vi Compressors
The calibration process for the capacity slide of a step variable Vi compressor package depends on the type of
compressor in use. The three types of compressors which may utilize step Variable Vi are Frick, Mycom and HE.
Touching the cell associated with the measured value of the capacity slide position on a step variable Vi com-
pressor will bring up the calibration display shown below.
fig.118:
Capacity Slide Calibration Pad (Step Variable Vi)
1. Ensure that the control panel is in
Service Mode
and the compressor is
Stopped
.
2. Verify that the compressor is physically fully unloaded. The GEA Omni™ will only allow the compressor to
start if it has a slide valve reading less than the value of the
Maximum Capacity to Allow Start
parameter.
3.
START
the Compressor.
4. Touch the
LOW
button to force the Vi setting of the compressor to its low level. The bar on the right edge of
the button will illuminate green to indicate that the Vi Setting is at its low.
5. Touch the
UNLOAD
button. Wait until the slide valve reaches the fully unloaded position. The
Capacity Slide
Voltage
should stabilize at approximately 1 V when the compressor is fully unloaded.
6. Touch the
Save Low Offset
button. The corresponding slide valve position sensor output has been recorded
as the fully unloaded position.
7. Touch the
LOAD
button. Wait until the slide valve reaches the fully loaded position. The
Slide Position Indi-
cator
should stabilize at approximately 5 V when the compressor is fully loaded.
8. Touch the
Save High Offset
button, the corresponding slide valve position sensor output has been recorded
as the fully loaded position.
9. Touch the
UNLOAD
button again. The compressor should fully unload and the indicated
Capacity Slide
Position
should track with it. Touch the
LOAD
button to fully load the compressor and observe the
Capacity
Slide Position
.
10. If the
Capacity Slide Position
appears to track the
Capacity Slide Voltage
, the calibration is complete.
11. Otherwise, repeat the procedure. Ensure that the
Slide Position Indicator
reading changes smoothly
between full unload and full load.
12. Touch the
Medium
button to force the compressor Vi setting to
Medium.
13. Repeat Steps 5 through 11.
14. Touch the
High
button to force the compressor Vi setting to
High.
15. Repeat Steps 5 through 11.
16. The compressor may be taken out of Service mode and stopped if desired.
Sensor Calibration
Capacity Slide Position Calibration
Instruction Manual | GEA Omni™
Control panel
230
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......