2.
Panel Data Report
Touching the button to the right of this section will generate a pdf document containing important infor-
mation on all analog and digital I/O associated with the panel. The information in the panel data report
includes:
•
AB
The Allen Bradley address of the given data point.
•
Modbus Address
The Modbus location which the user may read from or write to for the given data point.
•
Description
The name associated with the given data point.
•
Designation/ Value
The I/O slice and channel associated with the given data point, if applicable.
Designation
is used for
analog data while
Value
is used for digital data.
•
Range
The maximum and minimum value that the given data point may contain. This column is only shown
for Analog data.
•
State
The reading that will be displayed for the given data point when it is energized or de-energized. This
column is only shown for digital data.
•
Scale
This column indicates the number of decimal points the chosen data point is configured to read.
•
R/W
This column determines whether the user may read or write to the given data point. An
R
indicates
that the data point is read-only, and may be viewed but not modified by the user.
R/W
indicates that
the data point is
Read/Write
enabled, meaning that the user may view and modify the value freely.
W
would indicate write-only, but is not used in the panel data report.
3.
Control Parameters
This section allows the user to save a specific set of parameter values to a USB or the panel. The table
to the left of the section displays all .oprms files found on the USB and panel memory which may be
used to restore parameters to the panel or delete parameter files from either location. The parameters
may be manipulated through the four buttons displayed at the bottom right of the screen. The buttons
are:
•
Back up to USB
This button is used to save the current values of all custom parameters on the panel to an .oprms file
in the GEA RT folder on the USB. If such a folder does not exist, it will be created automatically. The
default name of the file is the number of the configuration, but a custom name may be entered into
the text field above the button.
User interface
File Manager
Instruction Manual | GEA Omni™
Control panel
86
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......