1.
Power Failure Restart Mode
This parameter is used to select what action the compressor should take in the event of a power outage. The
options are:
•
Disabled
If this option is selected, the compressor will do nothing following a power outage.
•
Local
If this option is selected, the compressor will start in local mode following a power outage.
•
Remote
If this option is selected, the compressor will start in remote mode following a power outage.
•
Shutdown
If this option is selected, the compressor will annunciate a shutdown condition following a power outage.
2.
Power Failure Restart Delay
This parameter is used to select the period of time the panel will wait after recovering from a power outage
before taking the action dictated in the
Power Failure Restart Mode
parameter. This parameter will only be
visible if the
Power Failure Restart Mode
parameter is set to an option other than
Disabled
. The value is
measured in seconds.
3.
Power Failure Restart Abort Timer
This parameter is used to select the maximum period of time that a power failure may persist before the
power failure restart function will be disabled. If the duration of a power outage exceeds this time period, the
panel will take no action once power is restored, regardless of the action dictated in the
Panel Failure
Restart Mode
parameter. In this condition, a
Power Failure Restart Abort
shutdown condition will be annunci-
ated. This parameter will only be visible if the
Power Failure Restart Mode
parameter is set to an option
other than
Disabled
. The value is measured in minutes.
3.1.24
Superheat
Parameter
Units
Minimum
Maximum
Default
Superheat Suction
Annunciations
Selection – See Description
High Suction Superheat
Shutdown
Kelvin
0.0 K
100.0 K
100.0 K
°F
0.0 °F
180.0 °F
180.0 °F
High Suction Superheat
Shutdown Timer
Seconds
0 s
900 s
80 s
Low Suction Superheat
Shutdown
Kelvin
0.0 K
100.0 K
0.0 K
°F
0.0 °F
180.0 °F
0.0 °F
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
148
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016