5.
Schedule table
This table displays all steps that will be executed by the compressor sequencer on the currently
selected level during normal panel operation.
fig.53:
Sequencer Schedule Table
a.
Current step
This icon indicates which step is currently being executed by the sequencer.
b.
Previous timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the previous step. This column will not appear if the
Hide
Timers
button has been clicked.
c.
Soak timer
This column contains the period of time that the sequencer must remain on the current step
before determining if it should step ahead to the next step, step back to the previous step, or
remain on the current step. This column will not appear if the
Hide Timers
button has been
clicked.
d.
Next timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the next step. This column will not appear if the
Hide Timers
button has been clicked.
e.
Compressor Devices
These columns each correspond to an individual compressor on the currently selected level.
The contents of each cell dictate what action the device will take during the associated step.
The options are:
–
Stop
This option will cause the compressor to deactivate during the associated step.
–
Stop With Wait on Drive Timers
This option will cause the compressor to stop if the period of time determined by the motor
start to start timer has fully elapsed. If the timer has not fully elapsed, the sequencer will
wait for the timer to finish before instructing the compressor to stop.
–
Load
User interface
Sequencer
Instruction Manual | GEA Omni™
Control panel
56
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016