3.1.2
Control
Parameter
Units
Minimum
Maximum
Default
Control Mode
Selection – See Description
Control Mode Select By Digital
Input
Selection – See Description
Set Point Location
Selection – See Description
Remote Set Point Units
Selection – See Description
Remote Control Value Units
Selection – See Description
Maximum Capacity Slide to Allow
Start Override
Percent
0 %
100 %
70 %
Maximum Capacity Slide to Allow
Start
Percent
0 %
100 %
5 %
Capacity Slide Failed to Unload
Shutdown Timer
Seconds
35 s
600 s
180 s
Capacity Control Delay
Seconds
0 s
120 s
15 s
Load Limitation Delay
Seconds
15 s
300 s
15 s
Sequencer Overwrite Local
Capacity Parameters
Selection – See Description
Zero Load Shutdown Timer
Seconds
0 s
600 s
120 s
Swing Compressor Control
Selection – See Description
Suction Bypass Timer
Seconds
0 s
60 s
30 s
Fast Unload Timer
Seconds
1 s
60 s
3 s
External Capacity Mode
Selection – See Description
Remote Control Interface
Selection – See Description
Suction Check Valve Close Assist
Pulse Timer
Seconds
5 s
120 s
10 s
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
109