3.
High Motor Winding Shutdown
This parameter is used to select the temperature value in any motor winding phase above which a high tem-
perature shutdown condition will be annunciated. This parameter will only be visible if motor winding temper-
ature monitoring is selected in the
Motor Temperature Safeties
field motor section of the configuration. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
4.
High Motor Winding Warning Offset
This parameter is used to set an offset value subtracted from the
High Motor Winding Shutdown
parameter.
If the temperature on either motor bearing exceeds this calculated value, a high temperature warning condi-
tion will be annunciated. This parameter will only be visible if motor winding temperature monitoring is
selected in the
Motor Temperature Safeties
field motor section of the configuration. The value is measured in
the panel temperature units as selected on the
Panel Settings
screen.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
121