Parameter
Units
Minimum
Maximum
Default
MPaG
0.010 MPaD
0.500 MPaD
0.103 MPaD
MPaA
kg/cm²G
0.10 kg/cm2D
5.10 kg/cm2D
1.05 kg/cm2D
kg/cm²A
High Oil Filter Differential Timer
Seconds
1 s
60 s
5 s
Illegal Oil Filter Differential Pres-
sure Warning Timer
Seconds
0 s
300 s
60 s
Oil Filter Pipe Loss Adjustment
barG
0.00 barD
6.89 barD
0.00 barD
barA
PSIG
0.0 PSID
100.0PSID
0.0 PSID
PSIA
kPaG
0 kPaD
689 kPaD
0 kPaD
kPaA
MPaG
0.000 MPaD
0.689 MPaD
0.000 MPaD
MPaA
kg/cm²G
0.00 kg/cm2D
7.03 kg/cm2D
0.00 kg/cm2D
kg/cm²A
1.
High Oil Filter Differential Shutdown
This parameter is used to select the maximum allowable differential in oil filter pressure while the compres-
sor is running or starting. If the differential exceeds this value a
High Oil Filter Differential Shutdown
will be
annunciated. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
2.
High Oil Filter Differential Warning Offset
This parameter is used to set an offset value subtracted from the
High Oil Filter Pressure Differential Shut-
down
value. If the differential exceeds this calculated value, a
High Oil Filter Differential Warning
will be
annunciated. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
3.
High Oil Filter Differential Timer
This parameter is used to select for what period of time the
High Oil Filter Differential
parameters will be
ignored after the compressor is started. The value is measured in seconds.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
131