GE Multilin
T60 Transformer Protection System
B-59
APPENDIX B
B.4 MEMORY MAPPING
B
B234
...Repeated for Received Analog 19
B236
...Repeated for Received Analog 20
B238
...Repeated for Received Analog 21
B23A
...Repeated for Received Analog 22
B23C
...Repeated for Received Analog 23
B23E
...Repeated for Received Analog 24
B240
...Repeated for Received Analog 25
B242
...Repeated for Received Analog 26
B244
...Repeated for Received Analog 27
B246
...Repeated for Received Analog 28
B248
...Repeated for Received Analog 29
B24A
...Repeated for Received Analog 30
B24C
...Repeated for Received Analog 31
B24E
...Repeated for Received Analog 32
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290
IEC 61850 Configurable Reports Dataset Items (64
items)
0 to 848
---
1
F615
0 (None)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500
Number of Status Indications in GGIO1
8 to 128
---
8
F001
8
B501
IEC 61850 GGIO1 Indication FlexLogic Operands (128
items)
---
---
1
F300
0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function (GoEna)
0 to 1
---
1
F102
1 (Enabled)
B5A1
IEC 61850 Configurable GOOSE ID
---
---
---
F209
“GOOSEOut_x_”
B5C2
Configurable GOOSE Destination MAC Address
---
---
---
F072
0
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B5C6
IEC 61850 Configurable GOOSE VLAN ID
0 to 4095
---
1
F001
0
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B5C8
IEC 61850 Configurable GOOSE ConfRev (Configuration
Revision)
1 to 4294967295
---
1
F003
1
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
0 to 3
---
1
F611
3 (Relaxed)
B5CB
Configurable GOOSE Dataset Items for Transmission
(64 items)
0 to 1008
---
1
F616
0 (None)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
B7B7
...Repeated for Module 6
B822
...Repeated for Module 7
B88D
...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 modules)
B900
Configurable GOOSE Dataset Items for Reception
(32 items)
0 to 197
---
1
F233
0 (None)
B920
...Repeated for Module 2
B940
...Repeated for Module 3
B960
...Repeated for Module 4
B980
...Repeated for Module 5
B9A0
...Repeated for Module 6
B9C0
...Repeated for Module 7
B9E0
...Repeated for Module 8
BA00
...Repeated for Module 9
BA20
...Repeated for Module 10
BA40
...Repeated for Module 11
BA60
...Repeated for Module 12
BA80
...Repeated for Module 13
BAA0
...Repeated for Module 14
Table B–10: MODBUS MEMORY MAP (Sheet 51 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...