GE Multilin
T60 Transformer Protection System
B-73
APPENDIX B
B.4 MEMORY MAPPING
B
D49D
PMU 1 Port 2 PHS-x Name (14 items)
---
---
---
F203
“GE-UR-PMU-PHS 1”
D50D
PMU 1 Port 3 PHS-x Name (14 items)
---
---
---
F203
“GE-UR-PMU-PHS 1”
D57D
PMU 1 Port 1 A-CH-x (8 items)
0 to 65535
---
1
F600
0
D585
PMU 1 Port 2 A-CH-x (8 items)
0 to 65535
---
1
F600
0
D58D
PMU 1 Port 3 A-CH-x (8 items)
0 to 65535
---
1
F600
0
D595
PMU 1 Port 1 A-CH-x Name (8 items)
---
---
---
F203
“AnalogChannel 1”
D5D5
PMU 1 Port 2 A-CH-x Name (8 items)
---
---
---
F203
“AnalogChannel 1”
D615
PMU 1 Port 3 A-CH-x Name (8 items)
---
---
---
F203
“AnalogChannel 1”
D655
PMU 1 Port 1 D-CH-x (16 items)
0 to 65535
---
1
F300
0
D665
PMU 1 Port 2 D-CH-x (16 items)
0 to 65535
---
1
F300
0
D675
PMU 1 Port 3 D-CH-x (16 items)
0 to 65535
---
1
F300
0
D685
PMU 1 Port 1 D-CH-x Name (16 items)
---
---
---
F203
“Dig Channel 1”
D705
PMU 1 Port 2 D-CH-x Name (16 items)
---
---
---
F203
“Dig Channel 1”
D785
PMU 1 Port 3 D-CH-x Name (16 items)
---
---
---
F203
“Dig Channel 1”
D805
PMU 1 Port 1 D-CH-x Normal State (16 items)
0 to 1
---
1
F108
0 (Off)
D815
PMU 1 Port 2 D-CH-x Normal State (16 items)
0 to 1
---
1
F108
0 (Off)
D825
PMU 1 Port 3 D-CH-x Normal State (16 items)
0 to 1
---
1
F108
0 (Off)
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4
PMU 1 Recording Clear Command
0 to 1
---
1
F126
0 (No)
E4D5
PMU 1 Recording Force Trigger
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC
PMU 1 Recording Rate
0 to 10
---
1
F544
3 (5/sec.)
E4DD
PMU 1 No of Timed Records
2 to 128
---
1
F001
10
E4DE
PMU 1 Trigger Mode
0 to 1
---
1
F542
0 (Auto Overwrite)
E4DF
PMU 1 Timed Trigger Position
1 to 50
%
1
F001
10
E4E0
PMU 1 Record PHS-1 (14 items)
0 to 14
---
1
F543
1 (Va)
E4EE
PMU 1 Record PHS-x Name (14 items)
---
---
---
F203
"GE-UR-PMU-PHS
1"
E55E
PMU 1 Record A-CH-x (8 items)
0 to 65535
---
1
F600
0
E566
PMU 1 Record A-CH-x Name (8 items)
---
---
---
F203
"AnalogChannel 1"
E5A6
PMU 1 Record D-CH-x (16 items)
0 to 65535
---
1
F300
0
E5B6
PMU 1 Record D-CH-x Name (16 items)
---
---
---
F203
"Dig Channel 1"
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
ECCC
PMU 1 Frequency Trigger Function
0 to 1
---
1
F102
0 (Disabled)
ECCD
PMU 1 Frequency Trigger Low Frequency
20 to 70
Hz
0.01
F001
4900
ECCE
PMU 1 Frequency Trigger High Frequency
20 to 70
Hz
0.01
F001
6100
ECCF
PMU 1 Frequency Trigger Pickup Time
0 to 600
s
0.01
F001
10
ECD0
PMU 1 Frequency Trigger Dropout Time
0 to 600
s
0.01
F001
100
ECD1
PMU 1 Frequency Trigger Block (3 items)
0 to 65535
---
1
F300
0
ECD4
PMU 1 Frequency Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
ECD5
PMU 1 Frequency Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Settings File Template (Read/Write Setting)
ED00
FlexLogic™ Displays Active
0 to 1
---
1
F102
1 (Enabled)
ED01
Reserved (6 items)
---
---
---
F205
(none)
Setting File Template (Read Only Non-Volatile)
ED07
Last Settings Change Date
0 to 4294967295
---
1
F050
0
Settings File Template (Read/Write Setting)
ED09
Template Bitmask (750 items)
0 to 65535
---
1
F001
0
Phasor Measurement Unit Records (Read Only)
EFFF
PMU Recording Number of Triggers
0 to 65535
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 65 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...