D-8
T60 Transformer Protection System
GE Multilin
D.1 IEC 60870-5-104 PROTOCOL
APPENDIX D
D
Counter freeze with reset
Counter reset
General request counter
Request counter group 1
Request counter group 2
Request counter group 3
Request counter group 4
Parameter loading:
Threshold value
Smoothing factor
Low limit for transmission of measured values
High limit for transmission of measured values
Parameter activation:
Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
Test procedure
File transfer:
File transfer in monitor direction:
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analog values
File transfer in control direction:
Transparent file
Background scan:
Background scan
Acquisition of transmission delay:
Acquisition of transmission delay
Definition of time outs:
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s
Maximum number of outstanding I-format APDUs
k
and latest acknowledge APDUs (
w
):
PARAMETER
DEFAULT
VALUE
REMARKS
SELECTED
VALUE
t
0
30 s
Timeout of connection establishment
120 s
t
1
15 s
Timeout of send or test APDUs
15 s
t
2
10 s
Timeout for acknowledgements in case of no data messages
t
2
<
t
1
10 s
t
3
20 s
Timeout for sending test frames in case of a long idle state
20 s
PARAMETER
DEFAULT
VALUE
REMARKS
SELECTED
VALUE
k
12 APDUs
Maximum difference receive sequence number to send state variable
12 APDUs
w
8 APDUs
Latest acknowledge after receiving
w
I-format APDUs
8 APDUs
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...