GE Multilin
T60 Transformer Protection System
5-23
5 SETTINGS
5.2 PRODUCT SETUP
5
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP / IEC104 POINT LISTS
ANALOG INPUT / MME POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A:
FlexAnalog Parameters
for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point
are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the T60 is restarted.
g) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
ANALOG INPUT / MME
POINTS
Point:
0
Off
Range: any FlexAnalog parameter
MESSAGE
Point:
1
Off
Range: any FlexAnalog parameter
↓
MESSAGE
Point:
255
Off
Range: any FlexAnalog parameter
IEC 61850 PROTOCOL
GSSE / GOOSE
CONFIGURATION
MESSAGE
SERVER
CONFIGURATION
MESSAGE
IEC 61850 LOGICAL
NODE NAME PREFIXES
MESSAGE
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
CONFIGURATION
MESSAGE
GGIO2 CONTROL
CONFIGURATION
MESSAGE
GGIO4 ANALOG
CONFIGURATION
MESSAGE
GGIO5 UINTEGER
CONFIGURATION
MESSAGE
REPORT CONTROL
CONFIGURATION
MESSAGE
XCBR
CONFIGURATION
MESSAGE
XSWI
CONFIGURATION
NOTE
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...