5-98
T60 Transformer Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
5.4.7 FLEXCURVES™
a) SETTINGS
PATH: SETTINGS
SYSTEM SETUP
FLEXCURVES
FLEXCURVE A(D)
FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.
FLEXCURVE A
FLEXCURVE A TIME AT
0.00 xPKP:
0 ms
Range: 0 to 65535 ms in steps of 1
Table 5–8: FLEXCURVE™ TABLE
RESET
TIME
MS
RESET
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
0.00
0.68
1.03
2.9
4.9
10.5
0.05
0.70
1.05
3.0
5.0
11.0
0.10
0.72
1.1
3.1
5.1
11.5
0.15
0.74
1.2
3.2
5.2
12.0
0.20
0.76
1.3
3.3
5.3
12.5
0.25
0.78
1.4
3.4
5.4
13.0
0.30
0.80
1.5
3.5
5.5
13.5
0.35
0.82
1.6
3.6
5.6
14.0
0.40
0.84
1.7
3.7
5.7
14.5
0.45
0.86
1.8
3.8
5.8
15.0
0.48
0.88
1.9
3.9
5.9
15.5
0.50
0.90
2.0
4.0
6.0
16.0
0.52
0.91
2.1
4.1
6.5
16.5
0.54
0.92
2.2
4.2
7.0
17.0
0.56
0.93
2.3
4.3
7.5
17.5
0.58
0.94
2.4
4.4
8.0
18.0
0.60
0.95
2.5
4.5
8.5
18.5
0.62
0.96
2.6
4.6
9.0
19.0
0.64
0.97
2.7
4.7
9.5
19.5
0.66
0.98
2.8
4.8
10.0
20.0
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...