5-256
T60 Transformer Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
•
The breaker status is open.
•
An elevated high frequency current condition occurs and the current subsequently drops out again.
The algorithm is illustrated in the state machine diagram shown below.
Figure 5–143: ALGORITHM ILLUSTRATION – STATE MACHINE TO DETECT RESTRIKE
In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes will be picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
•
BREAKER RESTRIKE 1 FUNCTION
: This setting enable and disables operation of the breaker restrike detection ele-
ment.
•
BRK RSTR 1 BLOCK
: This setting is used to block operation of the breaker restrike detection element.
•
BREAKER RESTRIKE 1 SOURCE
: This setting selects the source of the current for this element. This source must
have a valid CT bank assigned.
•
BREAKER RESTRIKE 1 PICKUP
: This setting specifies the pickup level of the overcurrent detector in per-unit values
of CT nominal current.
•
BREAKER RESTRIKE 1 RESET DELAY
: This setting specifies the reset delay for this element. When set to “0 ms”,
then FlexLogic™ operand will be picked up for only 1/8th of the power cycle.
•
BRK RSTR 1 BRK OPEN
: This setting assigns a FlexLogic™ operand indicating the open position of the breaker. It
must be logic “1” when breaker is open.
•
BRK RSTR 1 OPEN CMD
: This setting assigns a FlexLogic™ operand indicating a breaker open command. It must be
logic “1” when breaker is opened, either manually or from protection logic.
•
BRK RSTR 1 CLS CMD
: This setting assigns a FlexLogic™ operand indicating a breaker close command. It must be
logic “1” when breaker is closed.
Capacitor bank
offline
Current
interruption
(overcurrent)
High-frequency
elevated current
Restrike detected:
OP state asserted
Breaker close
Breaker
close
Breaker
close
Capacitor bank
online
Current
interruption
(overcurrent)
Breaker open
command or breaker
open state
834768A1.CDR
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...