GE Multilin
3.4 MANAGED ETHERNET SWITCH MODULES
3 HARDWARE
3
Alternately, you can open a command window (type “cmd” from the
Run
item in the Start menu) and enter the
ipconfig
command.
6.
Now that the PC should be able to communicate to the UR relay through the UR Setup software.
c) INITIAL ETHERNET SWITCH MODULE SETUP
This procedure describes how to configure the T60 switch module through EnerVista UR Setup. Before starting this proce-
dure, ensure that the local PC is properly configured on the same network as the T60 device as shown in the previous sec-
tion.
1.
Launch the EnerVista UR Setup software.
2.
Click the
Device Setup
button.
3.
Click the
Add Site
button. This will launch the Device Setup window.
4.
Set the
Interface
option to “Ethernet” and enter the
IP Address
,
Slave Address
, and
Modbus Port
values as shown
below.
5.
Click the
Read Order Code
button. You should be able to communicate with the T60 device regardless of the value of
the Ethernet switch IP address and even though the front panel display states that the Ethernet module is offline.
1HZVLWH
2OGVLWH
,QWHUIDFHLV(WKHUQHWQRZ
0DNHVXUHWKHVHVHWWLQJV
DUHFRUUHFW
$&'5
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...